HV Outdoor Solid-Dielectric Vacuum Breakers (123KV)

Property Specification

Type: High-Voltage Solid-Dielectric Vacuum Circuit Breaker ( Up to 123 kV, 3150 A, 31.5 kA)

Features: Built with eco-friendly solid dielectric insulation encapsulating high-capacity vacuum interrupters, fully eliminating the risk of SF6 gas leakage, mixed gases, or insulating oil hazards. Features high-grade impact-resistant polymeric composite outdoor bushings, delivering exceptional dielectric endurance with a 550 kV BIL lightning impulse level and a 265 kV power-frequency withstand (over open contact at 50 Hz).

Applications: Adaptable across modular configurations, including 1-pole for medium/high-voltage distribution networks, 2-pole for railway catenary and traction power feeder stations, and 3-pole for 123 kV utility transmission lines, power generation facilities, grid substations, and renewable energy integration projects (wind and solar farms).

Description

Technical Data & Electrical Specifications

Performance Parameter / Engineering Feature Ratings & Specifications 
Equipment Classification Outdoor Vacuum Circuit Breaker
Phase / Pole Configurations 1, 2, or 3 Phases
Actuating / Operating Drive Heavy-duty steel spring mechanism
Bushing / Insulator Material High-grade anti-tracking polymeric composite
Rated Operating Frequency 50 / 60 Hz
Maximum Operating Altitude Up to 2000 m above sea level
Rated System Voltage 126 kV
Arc-Quenching & Interrupter Medium Sealed vacuum bottle
Rated Continuous Operational Current 3150 A / 4000 A (transformer capacity matched)
Power-Frequency Withstand Voltage (50 Hz / 1 min) 230 kV (to earth) / 265 kV (across open contacts)
Lightning Impulse Withstand Voltage (BIL, 1.2/50 μs) 550 kV (to earth) / 630 kV (across open contacts)
Rated Symmetrical Breaking Current 31.5 kA / 40 kA
Rated Peak Short-Circuit Making Current 85 kA / 100 kA
Total Closing / Making Duration ≤50 ms
Total Tripping / Breaking Duration ≤30 ms
Longitudinal Static Mechanical Load  1000 N
Transverse Cross-Sectional Static Load 700 N
Vertical Static Mechanical Load 700 N
Total External Creepage Distance 3970 mm
Standard Rated Operating Duty Cycle O-0.3s-CO-3 min-CO
Trip & Close Coil Control Supply Voltage 48, 60, 72, 110, 220 V DC
Charging Motor Supply Voltage 48, 60, 72, 110, 220 V DC
Drive Motor Power Rating 600 W
Closing Coil Quantity & Consumption 1 X Coil (400 W power rating)
Tripping Coil Quantity & Consumption 2 X Coils (400 W power rating each)
Auxiliary Blocking Contacts (NO / NC) 12 NO (12X) / 12 NC (12X)
Mechanical Switching Endurance 10,000 operational cycles
Manual Open / Close Pushbuttons on Drive Integrated as standard (Yes)
Local / Remote Electrical Selector Switch Integrated as standard (Yes)
Control Cabinet Open / Close Buttons with LEDs Integrated as standard (Yes)
Overall Dimensions (H X L X W) 5360 X (2480–4260) X 690 mm
Auxiliary Service Supply (Internal Heaters, Lighting) 110, 220 V DC / V AC