NYY 0.6/1 kV Multi-Core Copper Cable

Property Specification
Type: YVV-U / YVV-R | NYY | Cu/PVC/PVC

Standards: IEC 60502-1,
Construction:Bare copper conductors, PVC insulation, PVC filler, PVC outer jacket

Applications: Designed for power distribution and mains lighting. Suitable for indoor installation, direct burial (underground), outdoor exposure, and cable ducts, provided there is no risk of high mechanical damage.

Description

Technical Specifications

Conductor Size (mm²) Overall Diameter (mm) Cable Weight (kg/km) Max. DC Resistance at 20°C (Ohm/km) Current Carrying Capacity in Ground (A) Current Carrying Capacity in Air (A)
2×1.5 10.5 150 12.1 32 22
2×2.5 11.5 190 7.41 42 30
2×4 13.0 260 4.61 52 40
2×6 14.0 320 3.08 66 50
2×10 16.0 460 1.83 90 69
2×16 18.0 620 1.15 115 92
2×25 22.0 920 0.727 150 118
2×35 24.0 1160 0.524 180 147
2×50 27.0 1550 0.387 215 180
2×70 31.0 2100 0.268 264 224
2×95 35.0 2800 0.193 318 271
2×120 39.0 3450 0.153 360 314
2×150 43.0 4200 0.124 406 361
2×185 47.0 5200 0.0991 458 412
2×240 53.0 6800 0.0754 537 484
WhatsApp Anfrage Get in touch