| Applicable Standard |
— |
IEC 61442 |
| Rated Voltage Class |
26/35 (40.5) kV |
— |
| Partial Discharge Test |
45 kV, ≤ 10 pC (@ ambient temp.) |
— |
| AC Withstand Voltage |
93.5 kV for 5 min |
— |
| Impulse Withstand Voltage |
200 kV (10 pos. / 10 neg. pulses @ 95°C–100°C) |
— |
| 36 kV (42 kV) Indoor Termination Kit |
35–150 mm² |
IEC 61442 & HD 629.1 S3:2019 |
|
95–240 mm² |
IEC 61442 & HD 629.1 S3:2019 |
|
185–400 mm² |
IEC 61442 & HD 629.1 S3:2019 |
| 36 kV (42 kV) Outdoor Termination Kit |
35–150 mm² |
IEC 61442 & HD 629.1 S3:2019 |
|
95–240 mm² |
IEC 61442 & HD 629.1 S3:2019 |
|
185–400 mm² |
IEC 61442 & HD 629.1 S3:2019 |
| 36 kV (42 kV) Straight-Through Joint Kit |
35–150 mm² |
IEC 61442 & HD 629.1 S3:2019 |
|
95–240 mm² |
IEC 61442 & HD 629.1 S3:2019 |
|
185–400 mm² |
IEC 61442 & HD 629.1 S3:2019 |