Indoor Busbar Current Transformer (Up to 17.5kV)

Property Specification

Type: Medium-Voltage Epoxy Resin Cast Indoor Bus-Type Current Transformer (Up to 17.5 kV)

Features: Epoxy resin cast construction rated for insulation voltages up to 17.5 kV, serving a dual function as a current transformer and an insulating bushing within switchboards. Configured with single or multiple transformation ratios with secondary reconnection options. Accommodates 1 to 6 secondary windings for metering and relay protection applications. Built with an integrated cast secondary terminal board and allows flexible installation in any mounting orientation using a four-screw fixation setup.

Applications: Medium-voltage indoor switchgear assemblies, distribution cubicles, busbar wall/compartment transitions, and primary power distribution networks requiring integrated bushing insulation alongside current measurement and protection monitoring.

Description

Technical Product Range & Performance Matrix

Technical Parameter / Feature Category Bus-Type Current Transformer Specifications
Nominal & Highest Equipment Voltage (Um)

• 12 kV Class (Rated voltages: 3.6 kV, 7.2 kV, 12 kV)

• 17.5 kV Class (Rated voltage: 17.5 kV)

Power-Frequency Withstand Test Voltage (1 min)

• 28 kV (for 12 kV Class)

• 38 kV (for 17.5 kV Class)

Lightning Impulse Withstand Test Voltage (1.2/50 µs)

• 75 kV (for 12 kV Class)

• 95 kV (for 17.5 kV Class)

Rated Continuous Thermal Current (Icth) Up to 4,000 A
Rated Primary Current Range (In)

500 A to 4,000 A

(Standard steps: 500, 600, 750, 1000, 1250, 1500, 2000, 2500, 3000, 3500, 4000 A; non-standard ratings available on request)

Rated Secondary Current 1 A, 5 A (configurable with combined values in a single unit)
Rated Short-Time Thermal Current (Ith, 1s) 90 kA
Rated Burdens & Accuracy Classes

• Burdens: 5 VA to 30 VA

• Metering Classes: 0.2, 0.5, 1

• Protection Classes: 5P, 10P

Reconnection Capabilities Secondary side only
Rated Frequency 50 Hz, 60 Hz