Single-Core Cu/XLPE/HFFR Cable (0.6/1 kV)

Property Specification
Type: N2XH
Standards: IEC 60502
Construction: Copper conductor, XLPE insulation, HFFR outer sheath
Applications: Designed for use in fire-sensitive locations and high-density public structures such as hotels, schools, high-rise buildings, hospitals, data centers, and commercial complexes.

Description

Technical Specifications

Conductor Size (mm²) Overall Diameter (mm) Cable Weight (kg/km) Max. DC Resistance at 20°C (Ohm/km) Current Carrying Capacity in Air (In Trefoil) (A) Current Carrying Capacity in Air (Laid Flat) (A)
1×4 6.5 70 4.61 56 40
1×6 7.0 90 3.08 71 53
1×10 8.5 130 1.83 100 74
1×16 9.5 195 1.15 135 100
1×25 11.0 290 0.727 180 133
1×35 12.0 380 0.524 225 167
1×50 13.5 500 0.387 273 205
1×70 16.0 710 0.268 350 265
1×95 17.0 950 0.193 428 325
1×120 19.0 1200 0.153 495 380
1×150 21.0 1400 0.124 575 442
1×185 23.5 1820 0.0991 660 510
1×240 26.0 2320 0.0754 780 605
1×300 28.0 3020 0.0601 864 690
1×400 32.0 3820 0.0470 1018 810
1×500 36.0 4850 0.0366 1173 930