0.6/1 kV Single-Core Power Cables with PVC Insulation

Property Specification
Type: NYY, Cu/PVC/PVC
Standards: IEC 60502-1
Construction: Copper core, PVC insulation layer, PVC outer jacket
Applications: Suitable for power distribution and street lighting networks, this cable is designed for indoor/outdoor use, direct underground placement, and cable conduit runs where severe mechanical strains are absent.

Description

Technical Specifications

Conductor Size (mm²) Overall Diameter (mm) Cable Weight (kg/km) Max. Conductor DC Resistance at 20°C (Ohm/km) Current Carrying Capacity Ground (Flat / Trefoil) (A) Current Carrying Capacity Air (Flat / Trefoil) (A)
1×4 7.5 90 4.61 56 / 48 45 / 32
1×6 8.0 110 3.08 70 / 60 58 / 40
1×10 9.5 160 1.83 95 / 80 78 / 60
1×16 10.0 220 1.15 123 / 105 108 / 80
1×25 11.5 320 0.727 160 / 137 140 / 110
1×35 13.0 425 0.524 190 / 162 175 / 135
1×50 14.0 550 0.387 225 / 192 210 / 165
1×70 16.0 760 0.268 272 / 235 270 / 210
1×95 18.0 1020 0.193 320 / 284 330 / 260
1×120 19.5 1280 0.153 375 / 320 385 / 300
1×150 22.0 1525 0.124 420 / 360 448 / 350
1×185 24.0 1950 0.0991 475 / 410 510 / 400
1×240 26.5 2450 0.0754 550 / 475 600 / 480
1×300 30.0 3175 0.0601 632 / 542 678 / 549
1×400 33.0 4050 0.0470 730 / 624 817 / 657
1×500 38.0 5150 0.0366 823 / 698 940 / 749