| Rated Apparent Power (@ 40°C) |
3500 kVA |
5000 kVA |
7000 kVA |
| Transformer Configuration |
Oil-Immersed (ONAN) |
Oil-Immersed (ONAN) |
Oil-Immersed (ONAN) |
| Vector Group / Winding Connection |
Dy11 |
Dy11 – y11 |
Dy11 – y11 |
| Low-Voltage / Medium-Voltage Range |
0.8 / 10 – 35 kV |
0.8 / 10 – 35 kV |
0.8 / 10 – 35 kV |
| Max Input Current at Rated Voltage |
2526 A |
2 × 1804 A |
2 × 2526 A |
| Transformer Peak Efficiency |
≥99% |
≥99% |
≥99% |
| Short-Circuit Impedance |
7.0% (±10%) |
7.0% (±10%) |
8.0% (±10%) |
| MV Switchgear Voltage / Rated Current |
12.0 – 40.5 kV / 630 A |
12.0 – 40.5 kV / 630 A |
12.0 – 40.5 kV / 630 A |
| LV Main Air Circuit Breaker (ACB) |
3200A / 800Vac / 3P (1 pc) |
3200A / 800Vac / 3P (2 pcs) |
3200A / 800Vac / 3P (2 pcs) |
| LV Branch Molded Case Breakers (MCCB) |
250A / 800Vac / 3P (14 pcs) |
250A / 800Vac / 3P (20 pcs) |
250A / 800Vac / 3P (28 pcs) |
| Surge / Overvoltage Protection |
AC Type I + II |
AC Type I + II |
AC Type I + II |
| Operating Thermal Envelope |
-25°C to +55°C (>40°C derating) |
-25°C to +55°C (>40°C derating) |
-25°C to +55°C (>40°C derating) |
| Enclosure Ingress / Corrosion Rating |
IP54 / C4H (Optional: C5M) |
IP54 / C4H (Optional: C5M) |
IP54 / C4H (Optional: C5M) |