Polymeric Metal-Oxide Surge Arresters

Property Specification

Type: Polymeric Metal-Oxide Surge Arrester (Overvoltage Protector)

Features: Designed for shunt connection with critical power assets, this polymer-housed surge arrester suppresses transient overvoltages to safeguard high-voltage electrical infrastructure, it maintains high resistance during normal operation without disturbing system power flow, exhibiting low leakage current, high thermal stability, and extended service life. The unit utilizes a direct-molded, gapless housing that guarantees full hermetic sealing against moisture ingress while providing exceptional pressure-relief explosion safety and high pollution performance. Its compact, shock-resistant design prevents transit damage.

Description

Technical Parameters

System Rated Voltage (kV r.m.s.) Maximum Continuous Operating Voltage (kV r.m.s.) Lightning Residual Voltage at Rated Current (kV peak) Line Discharge Category Minimum Creepage Length (mm) 2 ms Rectangular Current Impulse Withstand (A) 4/10 µs High-Current Surge Rating (kA peak)
6 5.1 18 320 150 65
9 7.65 27 430 150 65
12 10.2 36 430 150 65
15 12.75 45 530 150 65
18 15.3 54 530 150 65
21 16.8 63 640 150 65
24 19.2 72 640 150 65
27 21.6 81 740 150 65
30 24 90 890 150 65
33 26.4 99 890 150 65
36 28.8 108 1115 150 65
6 5.1 18 1 320 250 100
9 7.65 27 1 430 250 100
12 10.2 36 1 430 250 100
15 12.75 45 1 530 250 100
18 15.3 54 1 530 250 100
21 16.8 63 1 640 250 100
24 19.2 72 1 740 250 100
27 21.6 81 1 740 250 100
30 24 90 1 890 250 100
33 26.4 99 1 890 250 100
36 28.8 108 1 1115 250 100
42 33.6 126 2 1260 400 100
48 39 139 2 1260 400 100
54 42 160 2 1260 400 100
60 48 178 2 1465 400 100
66 52.8 196 2 1465 400 100
72 57 214 2 2255 400 100
84 67.2 244 2 2255 400 100
90 72.5 249 2 2255 400 100
96 75 265 3 3555 800 100
108 84 281 3 3555 800 100
120 96 300 3 4153 800 100
150 120 416 3 5040 800 100
200 156 520 3 7110 800 100
108 84 281 3 3555 800 100
120 96 300 3 4153 800 100
150 120 416 3 5040 800 100
200 156 520 3 7110 800 100