Outdoor Single-Pole Cast Resin Voltage Transformer (Up to 24kV )

Property Specification

Type: Outdoor Cast Resin Single-Pole Insulated Voltage Transformer (Up to 24 kV)

Features: Engineered with advanced winding and shielding techniques to optimize electric stress distribution, this unit utilizes layered inter-coil insulation and complete encapsulation in hydrophobic cycloaliphatic epoxy (HCEP). The HCEP material delivers high mechanical strength alongside superior resistance to UV exposure, ozone, arc tracking, and moisture accumulation, ensuring long-term reliability in humid or severe outdoor weather conditions. Built on a rigid support frame, the assembly incorporates dual secondary windings for metering, protective relaying, or open-delta grounding connections, and accommodates an operational overvoltage rating of 1.9 X Un for 8 hours.

Applications: Outdoor power distribution networks up to 24 kV, phase-to-ground voltage measurement, system protection relaying, residual voltage detection via open-delta configurations, and outdoor substations operating in high-moisture or polluted environments.

Description

Transposed Technical Comparison Matrix

Technical Parameter / Feature Category Single-Pole Outdoor Voltage Transformer Performance Specifications
Maximum Equipment Voltage (Um) Up to 24 kV
Power-Frequency Withstand Rating (1 min) Up to 60 kV
Lightning Impulse Withstand Level (Peak) Up to 150 kV
Rated Primary Line-to-Ground Voltage (Un) Up to 22/√3 kV (tailored ratings available upon request)
Overvoltage Capability Factor 1.9 X Un / 8 hours
Maximum Secondary Winding Count Up to 2 secondary windings
Secondary Winding Outputs

Metering Circuit: Up to 230/√3 V

Open-Delta Auxiliary Circuit: Up to 230/3 V

Combined Maximum Burden / Accuracy Grades

Class 0.2: 25 VA

Class 0.5: 50 VA

Class 1: 100 VA

Class 3: 150 VA

Class 3P Protection: 150 VA

Class 6P Protection: 200 VA

Continuous Thermal Power Output 500 VA
External Insulation Creepage Distance 800 mm
Estimated Unit Mass Approximately 39 kg
Ambient Thermal Operating Range -40^C to +40^C
Rated Operational Frequency 50 Hz / 60 Hz