Description
Technical Product Range & Performance Matrix
| Technical Parameter / Feature Category | Outdoor Current Transformer Specifications |
| Rated Voltage Classes & Insulation Levels |
• 17.5 kV Class: 12/28/75 kV, 17.5/38/95 kV, 17.5/42/110 kV • 24 kV Class: 12/28/75 kV, 17.5/38/95 kV, 24/50/125 kV, 24/60/150 kV |
| Rated Primary Current Range (In) |
• Standard Models: 1,250 A (extended rating up to 120%) • High-Capacity Models: 1,250 A (extended rating up to 150%), 1,875 A (extended rating 100%) (Custom primary currents available on special request) |
| Rated Secondary Current | 1 A, 5 A (combinations allowed in a single transformer) |
| Rated Short-Time Thermal Current (Ith, 1s) |
• Standard Models: Up to 31.5 kA • High Short-Circuit Models: Up to 63 kA |
| Reconnection Options | Secondary side only, or dual Primary / Secondary reconnection |
| Rated Output Burdens & Accuracy Classes |
• Output Burden: 1 VA to 60 VA • Metering Classes: 0.2, 0.2S, 0.5, 0.5S, 1, 3 • Protection Classes: 5P, 10P, Class PX |
| Operational & Environmental Limits |
• Rated Frequency: 50 Hz, 60 Hz • Ambient Operating Temperature: -60°C to +55°C • Insulation Class: Class E |
| Physical Characteristics & Creepage |
• Weight: 24 kg to 43 kg (depending on frame size and voltage rating) • Creepage Distance: 600 mm (17.5 kV class) / 800 mm (24 kV class) |