Outdoor Double-Pole Cast Resin Voltage Transformer (24–40.5kV)

Property Specification

Type: Outdoor Cast Resin Double-Pole Insulated Voltage Transformer (24 kV – 40.5 kV)

Features: Manufactured with precision coil winding and electrostatic shielding techniques for optimized dielectric stress distribution, this unit is mounted on a heavy-duty internal support structure. The entire core and coil assembly is cast into hydrophobic cycloaliphatic epoxy resin (HCEP) through automated pressure gelation processes, providing superior mechanical strength and outstanding resistance to ultraviolet radiation, ozone, and surface tracking. Its water-repellent outer surface ensures stable dielectric performance in rain, fog, and high-humidity conditions. Standard models feature a single secondary winding for metering, with dual-winding configurations available; accessible grounding terminals are provided for safe operation.

Applications: Outdoor medium voltage distribution systems up to 40.5 kV, phase-to-phase voltage measurement, open-delta/V-connected phase monitoring, outdoor utility switching yards, and power metering in harsh, high-humidity environments.

Description

Comparative Technical Matrix

Technical Parameter / Specification Category Double-Pole Outdoor Voltage Transformer Performance Specifications
Maximum Equipment Voltage Rating (Um)

24 kV Class: Up to 24 kV

40.5 kV Class: Up to 40.5 kV

Short-Duration Power Frequency Withstand Voltage (1 min)

24 kV Class: Up to 50 kV

40.5 kV Class: Up to 95 kV

Peak Impulse Withstand Voltage Rating

24 kV Class: Up to 170 kV

40.5 kV Class: Up to 200 kV

Rated Primary Voltage Spectrum (Un)

24 kV Class: Up to 22 kV

40.5 kV Class: Up to 38 kV

Overvoltage Factor Operating Capability

24 kV Class: 1.2 x Un continuous or 1.5 x Un / 30s

40.5 kV Class: 1.2 x Un continuous

Maximum Secondary Circuit Capacity Up to 2 secondary windings (standard range 100 V – 120 V; custom outputs available)
Secondary Voltage Capacity Up to 230 V
Rated Output (VA) / Accuracy Class Distribution

24 kV Class: 30 VA / Class 0.250 VA / Class 0.5100 VA / Class 1500 VA / Class 3

40.5 kV Class: 50 VA / Class 0.2100 VA / Class 0.5200 VA / Class 1500 VA / Class 3, 3P, 6P

Continuous Thermal Limiting Output

24 kV Class: 500 VA

40.5 kV Class: 700 VA

External Insulation Creepage Distance

24 kV Class: 800 mm

40.5 kV Class: 1325 mm

Estimated Net Weight

24 kV Class: Approx. 43 kg

40.5 kV Class: Approx. 70 kg

Ambient Thermal Range -40°C to +40°C
Operating Frequency Range 50 Hz / 60 Hz