Description
Technical Product Range & Performance Matrix
| Technical Parameter / Feature Category | Double-Pole Indoor Voltage Transformer Specifications |
| Highest Equipment Voltage (Um) |
• Low-Voltage Class: 3.6 kV – 12 kV • Medium-Voltage Class: 12 kV – 17.5 kV • High-Voltage Class: 17.5 kV – 24 (25) kV |
| Power-Frequency Withstand Voltage (1 min) |
• Low-Voltage Class: 10 kV – 42 kV • Medium-Voltage Class: 28 kV – 38 kV • High-Voltage Class: 38 kV – 50 (55) kV |
| Lightning Impulse Withstand Voltage |
• Low-Voltage Class: 40 kV – 75 kV • Medium-Voltage Class: 75 kV – 95 kV • High-Voltage Class: 95 kV – 125 kV |
| Rated Primary Voltages |
• Low-Voltage Range: 3 kV, 3.3 kV, 6 kV, 6.6 kV, 10 kV, 11 kV • Medium-Voltage Range: 10 kV, 11 kV, 13.8 kV • High-Voltage Range: 11 kV, 15 kV, 20 kV, 22 kV (Custom ratings available upon request) |
| Rated Secondary Voltages & Accuracy Classes |
• Secondary Voltages: 100 V, 110 V (custom ratings available on request) • Metering Classes: 0.2, 0.5, 1 • Protection Classes: 3P, 6P |
| Maximum Output Burdens |
• Low & Medium Voltage: 25 VA / 0.2 – 75 VA / 0.5 – 150 VA / 1 • High Voltage: 50 VA / 0.2 – 150 VA / 0.5 – 200 VA / 1 |
| Operational Frequency Limits | 50 Hz, 60 Hz |