36–42kV Outdoor Cable Terminations kit

Property Specification
Type: Medium-Voltage Heat Shrink Outdoor Cable Termination Kit (36 kV / 42 kV Class)
Standards: HD 629.1 S3, IEC 61442
Features: Engineered to provide high mechanical strength capable of withstanding dynamic physical stresses and harsh open-air environments. Features a compact, streamlined footprint compatible with diverse conductor cross-sections and connector configurations. Delivers outstanding resistance to UV radiation, moisture, and severe weathering, allowing immediate power restoration upon completion of installation. Maintains long-term storage integrity when kept within temperature limits
Applications: Specifically configured for outdoor terminating and sealing of medium-voltage power cables connected to overhead lines, outdoor switchgear, transformers, and pole-mounted equipment operating up to 36 kV (42 kV).

Description

Technical Specifications & Product Range

Product / Parameter Category Specification / Conductor Range Standards & Test Criteria
Applicable Standard IEC 61442
Rated Voltage Class 26/35 (40.5) kV
Partial Discharge Test 45 kV, 10 pC (@ ambient temp.)
AC Withstand Voltage 93.5 kV for 5 min
Impulse Withstand Voltage 200 kV (10 pos. / 10 neg. pulses @ 95°C–100°C)
36 kV (42 kV) Indoor Termination Kit 35–150 mm² IEC 61442 & HD 629.1 S3:2019
95–240 mm² IEC 61442 & HD 629.1 S3:2019
185–400 mm² IEC 61442 & HD 629.1 S3:2019
36 kV (42 kV) Outdoor Termination Kit 35–150 mm² IEC 61442 & HD 629.1 S3:2019
95–240 mm² IEC 61442 & HD 629.1 S3:2019
185–400 mm² IEC 61442 & HD 629.1 S3:2019
36 kV (42 kV) Straight-Through Joint Kit 35–150 mm² IEC 61442 & HD 629.1 S3:2019
95–240 mm² IEC 61442 & HD 629.1 S3:2019
185–400 mm² IEC 61442 & HD 629.1 S3:2019