123–145kV Dead-Tank Vacuum Breakers

Property Specification

Type: High-Voltage Dead-Tank Vacuum Circuit Breaker / Eco-Friendly F-Gas-Free Series (up to 145 kV / 123 kV )

Features: Utilizes state-of-the-art high-voltage vacuum interruption and clean-air dielectric insulation to deliver a completely climate-neutral footprint , delivering breaking capacities up to 63 kA and continuous current ratings up to 3150 A with rapid 2-cycle fault clearing. Features a 1:1 drop-in physical footprint identical to traditional SF6 dead-tank units for effortless retrofit without civil alterations. Eliminates regulatory gas reporting, pressure density monitoring, toxic decomposition hazards, and costly gas recovery/recycling processes while providing reliable cold-weather operation without tank heating systems.

Applications: Engineered for outdoor high-voltage utility substations, modern grid transmission infrastructure, power generation stations, renewable energy collection substations (wind/solar), and industrial power distribution systems transitioning to sustainable,

Description

Technical Data & Performance Specifications

Technical Parameter / Specification DT 123 kV DT 145 kV
Rated Maximum System Voltage 123 kV 145 kV
Full Short-Circuit Breaking Operations 30 cycles 30 cycles
Vacuum Interrupters per Phase / Pole 1 unit 1 unit
Rated Continuous Operational Current Up to 3150 A Up to 3150 A
Rated Fault Interruption Duration 2-cycle or 3-cycle options 2-cycle or 3-cycle options
Short-Time Withstand Current (1–3s) Up to 40 kA / 63 kA* Up to 40 kA / 63 kA*
Rated System Operating Frequency 50 / 60 Hz 50 / 60 Hz
Short-Duration Power-Frequency Withstand Voltage 260 kV 275 kV
Lightning Impulse Withstand Voltage (BIL) 550 kV 650 kV
Rated Short-Circuit Duration (tk) 3 s 3 s
Peak Dynamic Withstand Current (2.7 p.u.) 108 kA 108 kA
First-Pole-to-Clear Factor (kpp) 1.5 / 1.3 p.u. 1.5 / 1.3 p.u.
Capacitive Switching Factor (kc) 1.4 p.u. 1.4 p.u.
Switching Impulse Withstand Voltage (SIL) 710 kV 838 kV
Operating Ambient Temperature Limits -60°C to +50°C -60°C to +50°C
Standard Rated Duty Cycle / Auto-Reclosing O-0.3s-CO-3min-CO or CO-15s-CO O-0.3s-CO-3min-CO or CO-15s-CO
Scheduled Maintenance & Inspection Interval 12 years / 7,000 switching operations 12 years / 10,000 switching operations
Main Tank Dielectric Insulation Medium Clean Air Clean Air
Fluorinated Greenhouse Gas (SF6/F-Gas) Content 0 kg 0 kg

Higher breaking capacity ratings (up to 63 kA) available depending on project configuration